MRT Gas Quality Daily Sample Report


 2023/05/02                         ENABLE MISSISSIPPI RIVER TRANSMISSION, LLC              PAGE:     1
 MVRP3020-53                                   GAS SAMPLE ANALYSIS                             MVNX3020
                                                                                               TIME: 15:00:546


         Location              Gas Day    Gravity    BTU     CO2 %    N2 %    Oxygen %   H2S %   Methane %  Ethane %  Propane %  I-Butane %  N-Butane %  Neo-Pentane %  I-Pentane %  N-Pentane %  Hexanes %  N-Heptane %  N-Octane %  N-Nonane %
                                                                                 O2                 C1         C2        C3                                   C5                                     C6          C7           C8          C9
  -----------------------     ----------  -------  -------  -------  -------  --------  -------  ---------  --------  ---------  ----------  ----------  -------------  -----------  -----------  ---------  -----------  ----------  ----------

  MRT M/L @ PERRYVILLE  @     2023/05/01  0.5858   1.02296  1.1907   00.6054  00.0000   00.0000  95.0241    02.9457   00.1779    00.0219     00.0162     00.0000        00.0053      00.0026      00.0045    00.0034      00.0016     00.0000
  MRT M/L @ MERAMEC_STR 3     2023/05/01  0.5836   1.02271  1.0558   00.6138  00.0000   00.0000  95.2155    02.9569   00.1382    00.0063     00.0083     00.0000        00.0015      00.0010      00.0010    00.0008      00.0003     00.0000
  SHATTUC - STREAM 1 @ 90     2023/05/01  0.5857   1.02134  1.1574   00.7432  00.0000   00.0000  95.0989    02.7133   00.1903    00.0384     00.0261     00.0000        00.0115      00.0049      00.0067    00.0050      00.0024     00.0000



 The information displayed above reflects daily average gas quality readings
 taken at key locations on the MRT system.  The dates shown above are the
 dates of the readings.  The readings are taken daily, and information from such
 readings is posted on the first day thereafter.  If on any reading day there
 are problems retrieving the data, the last reported readings will remain
 posted until such time as new readings are obtained.  Due to factors such as
 equipment failure, sample contamination and human error, the information
 displayed above may not be completely accurate.